Friberg BE, Burman LG, Friberg S. Zoned exponential, vertical and horizontal ultra-clean laminar airflows. No differences in bacteriological efficiency.
ACTA ORTHOPAEDICA SCANDINAVICA 1998;
69:169-72. [PMID:
9602777 DOI:
10.3109/17453679809117621]
[Citation(s) in RCA: 10] [Impact Index Per Article: 0.4] [Reference Citation Analysis] [Abstract] [MESH Headings] [Track Full Text] [Subscribe] [Scholar Register] [Indexed: 11/13/2022]
Abstract
We compared the novel zoned exponential ultra-clean operating room ventilation, needing no extra side-walls with the traditionally used ultra-clean air systems having vertical or horizontal laminar airflow, but requiring extra side-walls. The three units were evaluated with regard to elimination of particles with focus on airborne and sedimenting bacteria-carrying particles (colony forming units, cfu) during rigidly standardized sham operations. Although minor differences were recorded inside the ultra-clean airflows, the three systems were comparable with regard to bacteriological efficiency and ensured a low air and surface contamination (0.05-4 cfu/m3 and 7-72 cfu/m2/h, depending on the site of sampling). We conclude that all three systems fulfilled well the criteria for ultra-clean air (< 10 cfu/m3), but that exponential airflow is the most versatile alternative, as additional side-walls around the operating area can be omitted.
Collapse