1
|
Crook B, Young C, Rideout C, Smith D. The Contribution of Legionella anisa to Legionella Contamination of Water in the Built Environment. INTERNATIONAL JOURNAL OF ENVIRONMENTAL RESEARCH AND PUBLIC HEALTH 2024; 21:1101. [PMID: 39200710 PMCID: PMC11354164 DOI: 10.3390/ijerph21081101] [Citation(s) in RCA: 0] [Impact Index Per Article: 0] [Reference Citation Analysis] [Abstract] [Key Words] [MESH Headings] [Grants] [Track Full Text] [Subscribe] [Scholar Register] [Received: 07/02/2024] [Revised: 08/15/2024] [Accepted: 08/16/2024] [Indexed: 09/02/2024]
Abstract
Legionella bacteria can proliferate in poorly maintained water systems, posing risks to users. All Legionella species are potentially pathogenic, but Legionella pneumophila (L. pneumophila) is usually the primary focus of testing. However, Legionella anisa (L. anisa) also colonizes water distribution systems, is frequently found with L. pneumophila, and could be a good indicator for increased risk of nosocomial infection. Anonymized data from three commercial Legionella testing laboratories afforded an analysis of 565,750 water samples. The data covered July 2019 to August 2021, including the COVID-19 pandemic. The results confirmed that L. anisa commonly colonizes water distribution systems, being the most frequently identified non-L. pneumophila species. The proportions of L. anisa and L. pneumophila generally remained similar, but increases in L. pneumophila during COVID-19 lockdown suggest static water supplies might favor its growth. Disinfection of hospital water systems was effective, but re-colonization did occur, appearing to favor L. pneumophila; however, L. anisa colony numbers also increased as a proportion of the total. While L. pneumophila remains the main species of concern as a risk to human health, L. anisa's role should not be underestimated, either as a potential infection risk or as an indicator of the need to intervene to control Legionella's colonization of water supplies.
Collapse
Affiliation(s)
- Brian Crook
- Science and Research Centre, Health and Safety Executive, Harpur Hill, Buxton, Derbyshire SK17 9JN, UK
| | - Charlotte Young
- Science and Research Centre, Health and Safety Executive, Harpur Hill, Buxton, Derbyshire SK17 9JN, UK
| | - Ceri Rideout
- Specialist Division Occupational Hygiene, Health and Safety Executive, Cardiff CF10 1EP, UK
| | - Duncan Smith
- Specialist Division Health Unit, Health and Safety Executive, Newcastle upon Tyne NE98 1YX, UK;
| |
Collapse
|
2
|
Schwaiger G, Matt M, Streich P, Bromann S, Clauß M, Elsner M, Seidel M. Standard addition method for rapid, cultivation-independent quantification of Legionella pneumophila cells by qPCR in biotrickling filters. Analyst 2024; 149:2978-2987. [PMID: 38602145 DOI: 10.1039/d3an02207b] [Citation(s) in RCA: 0] [Impact Index Per Article: 0] [Reference Citation Analysis] [Abstract] [MESH Headings] [Track Full Text] [Journal Information] [Subscribe] [Scholar Register] [Indexed: 04/12/2024]
Abstract
Cultivation-independent molecular biological methods are essential to rapidly quantify pathogens like Legionella pneumophila (L. pneumophila) which is important to control aerosol-generating engineered water systems. A standard addition method was established to quantify L. pneumophila in the very complex matrix of process water and air of exhaust air purification systems in animal husbandry. Therefore, cryopreserved standards of viable L. pneumophila were spiked in air and water samples to calibrate the total bioanalytical process which includes cell lysis, DNA extraction, and qPCR. A standard addition algorithm was employed for qPCR to determine the initial concentration of L. pneumophila. In mineral water, the recovery rate of this approach (73%-134% within the concentration range of 100-5000 Legionella per mL) was in good agreement with numbers obtained from conventional genomic unit (GU) calibration with DNA standards. In air samples of biotrickling filters, in contrast, the conventional DNA standard approach resulted in a significant overestimation of up to 729%, whereas our standard addition gave a more realistic recovery of 131%. With this proof-of-principle study, we were able to show that the molecular biology-based standard addition approach is a suitable method to determine realistic concentrations of L. pneumophila in air and process water samples of biotrickling filter systems. Moreover, this quantification strategy is generally a promising method to quantify pathogens in challenging samples containing a complex microbiota and the classical GU approach used for qPCR leads to unreliable results.
Collapse
Affiliation(s)
- Gerhard Schwaiger
- Institute of Water Chemistry, Chair of Analytical Chemistry and Water Chemistry, Technical University of Munich, Lichtenbergstraße 4, 85748 Garching, Germany.
| | - Marco Matt
- Institute of Water Chemistry, Chair of Analytical Chemistry and Water Chemistry, Technical University of Munich, Lichtenbergstraße 4, 85748 Garching, Germany.
| | - Philipp Streich
- Institute of Water Chemistry, Chair of Analytical Chemistry and Water Chemistry, Technical University of Munich, Lichtenbergstraße 4, 85748 Garching, Germany.
| | - Sarah Bromann
- Thuenen-Institute for Agricultural Technology, Bundesallee 47, D-38116 Braunschweig, Germany
| | - Marcus Clauß
- Thuenen-Institute for Agricultural Technology, Bundesallee 47, D-38116 Braunschweig, Germany
| | - Martin Elsner
- Institute of Water Chemistry, Chair of Analytical Chemistry and Water Chemistry, Technical University of Munich, Lichtenbergstraße 4, 85748 Garching, Germany.
| | - Michael Seidel
- Institute of Water Chemistry, Chair of Analytical Chemistry and Water Chemistry, Technical University of Munich, Lichtenbergstraße 4, 85748 Garching, Germany.
| |
Collapse
|
3
|
Lee ALH, Leung ECM, Wong BWH, Wong LCH, Wong YLY, Hung RKY, Ho SSY, Chow VCY. Clean clothes or dirty clothes? Outbreak investigation of carbapenem-resistant Acinetobacter baumannii related to laundry contamination through multilocus sequence typing (MLST). Infect Control Hosp Epidemiol 2023; 44:1274-1280. [PMID: 36345791 DOI: 10.1017/ice.2022.255] [Citation(s) in RCA: 1] [Impact Index Per Article: 1.0] [Reference Citation Analysis] [Abstract] [MESH Headings] [Track Full Text] [Journal Information] [Subscribe] [Scholar Register] [Indexed: 11/10/2022]
Abstract
OBJECTIVE To investigate the source in an outbreak of carbapenem-resistant Acinetobacter baumannii (CRA) in a general hospital due to contamination of a laundry evaporative cooler and the laundry environment using multilocus sequence typing (MLST). METHODS For CRA culture, clinical samples were collected from infected patients and close contacts, and environmental sampling was performed in patient surroundings and laundry facilities. MLST was used for the molecular typing of representative CRA isolates. Bacterial isolates with identical sequence types were considered epidemiologically linked and attributable to the same source. OXA genes in Acinetobacter baumannii were detected using polymerase chain reaction (PCR). RESULTS In total, 58 patients were affected in this outbreak. The mean patient age was 75.3, and 50% were female. The most common diagnoses at admission were skin and soft-tissue infection (n = 12, 20.7%) and pneumonia (n = 12, 20.7%). OXA-23 was positive in 64.7% of isolates. A CRA isolate from the evaporative cooler in the laundry was identical to that of 11 patients across 3 wards, belonging to ST345. Isolates from 3 laundry linen racks were identical to those of 7 patients from 3 wards, classified as ST1145. Isolates found on another linen rack and a pajama shelf were identical to isolates from 3 other patients from 2 wards, belonging to ST2207. There was no significant difference between sequence type distributions of clinical and environmental isolates (P = .12), indicating high likelihood of CRA originating from the same source. CONCLUSIONS MLST confirmed that contamination of the laundry evaporative cooler and surrounding environment caused a polyclonal CRA hospital outbreak. Hospital laundry is an important area for infection control and outbreak investigations of CRA.
Collapse
Affiliation(s)
| | | | | | | | | | - Rosana Ka Yin Hung
- Infection Control Team, New Territories East Cluster, Hospital Authority, Hong Kong
| | - Sindy Sin Yee Ho
- Infection Control Team, New Territories East Cluster, Hospital Authority, Hong Kong
| | - Viola Chi Ying Chow
- Department of Microbiology, Prince of Wales Hospital, Hong Kong
- Infection Control Team, New Territories East Cluster, Hospital Authority, Hong Kong
| |
Collapse
|
4
|
Monitoring PM2.5 at a Large Shopping Mall: A Case Study in Macao. Processes (Basel) 2023. [DOI: 10.3390/pr11030914] [Citation(s) in RCA: 0] [Impact Index Per Article: 0] [Reference Citation Analysis] [Abstract] [Track Full Text] [Journal Information] [Subscribe] [Scholar Register] [Indexed: 03/19/2023] Open
Abstract
Employees work long hours in an environment where the ambient air quality is poor, directly affecting their work efficiency. The concentration of particulate matters (PM) produced by the interior renovation of shopping malls has not received particular attention in Macao. Therefore, this study will investigate the indoor air quality (IAQ), in particular of PM2.5, in large-scale shopping mall renovation projects. This study collected on-site PM data with low-cost portable monitoring equipment placed temporarily at specific locations to examine whether the current control measures are appropriate and propose some improvements. Prior to this study, there were no measures being implemented, and on-site monitoring to assess the levels of PM2.5 concentrations was non-existent. The results show the highest level of PM2.5 recorded in this study was 559.00 μg/m3. Moreover, this study may provide a reference for decision-makers, management, construction teams, design consultant teams, and renovation teams of large-scale projects. In addition, the monitoring of IAQ can ensure a comfortable environment for employees and customers. This study concluded that the levels of PM2.5 concentration have no correlation with the number of on-site workers, but rather were largely influenced by the processes being performed on-site.
Collapse
|
5
|
Gea-Izquierdo E, Gil-de-Miguel Á, Rodríguez-Caravaca G. Legionella pneumophila Risk from Air–Water Cooling Units Regarding Pipe Material and Type of Water. Microorganisms 2023; 11:microorganisms11030638. [PMID: 36985212 PMCID: PMC10053303 DOI: 10.3390/microorganisms11030638] [Citation(s) in RCA: 0] [Impact Index Per Article: 0] [Reference Citation Analysis] [Abstract] [Track Full Text] [Journal Information] [Subscribe] [Scholar Register] [Received: 01/22/2023] [Revised: 02/27/2023] [Accepted: 02/28/2023] [Indexed: 03/06/2023] Open
Abstract
Legionellosis is a respiratory disease related to environmental health. There have been manifold studies of pipe materials, risk installations and legionellosis without considering the type of transferred water. The objective of this study was to determine the potential development of the causative agent Legionella pneumophila regarding air–water cooling units, legislative compliance, pipe material and type of water. Forty-four hotel units in Andalusia (Spain) were analysed with respect to compliance with Spanish health legislation for the prevention of legionellosis. The chi-square test was used to explain the relationship between material–water and legislative compliance, and a biplot of the first two factors was generated. Multiple correspondence analysis (MCA) was performed on the type of equipment, legislative compliance, pipe material and type of water, and graphs of cases were constructed by adding confidence ellipses by categories of the variables. Pipe material–type of water (p value = 0.29; p < 0.05) and legislative compliance were not associated (p value = 0.15; p < 0.05). Iron, stainless steel, and recycled and well water contributed the most to the biplot. MCA showed a global pattern in which lead, iron and polyethylene were well represented. Confidence ellipses around categories indicated significant differences among categories. Compliance with Spanish health legislation regarding the prevention and control of legionellosis linked to pipe material and type of water was not observed.
Collapse
Affiliation(s)
- Enrique Gea-Izquierdo
- Preventive Medicine and Public Health, Rey Juan Carlos University, 28922 Madrid, Spain
- Maria Zambrano Program, European Union, Spain
- Correspondence:
| | - Ángel Gil-de-Miguel
- Preventive Medicine and Public Health, Rey Juan Carlos University, 28922 Madrid, Spain
- CIBER of Respiratory Diseases (CIBERES), Instituto de Salud Carlos III, 28029 Madrid, Spain
| | - Gil Rodríguez-Caravaca
- Preventive Medicine and Public Health, Rey Juan Carlos University, 28922 Madrid, Spain
- Department of Preventive Medicine, Hospital Universitario Fundación Alcorcón, Universidad Rey Juan Carlos, 28922 Madrid, Spain
| |
Collapse
|
6
|
Evaluation of a Most Probable Number Method for Detection and Quantification of Legionella pneumophila. Pathogens 2022; 11:pathogens11070789. [PMID: 35890033 PMCID: PMC9324539 DOI: 10.3390/pathogens11070789] [Citation(s) in RCA: 0] [Impact Index Per Article: 0] [Reference Citation Analysis] [Abstract] [Key Words] [Track Full Text] [Download PDF] [Figures] [Journal Information] [Subscribe] [Scholar Register] [Received: 06/16/2022] [Revised: 07/02/2022] [Accepted: 07/07/2022] [Indexed: 11/17/2022] Open
Abstract
The detection and enumeration of Legionella pneumophila (L. pneumophila) in water is crucial for water quality management, human health and has been a research hotspot worldwide. Due to the time-consuming and complicated operation of the plate culture method, it is necessary to adopt a fast and effective method for application. The present study aimed to comprehensively evaluate the performance and applicability of the MPN method by comparing its qualitative and quantitative results with the GB/T 18204.5-2013 and ISO methods, respectively. The qualitative results showed that 372 samples (53%) were negative for both methods; 315 samples (45%) were positively determined by the MPN method, compared with 211 samples (30%) using GB/T 18204.5-2013. The difference in the detection rate between the two methods was statistically significant. In addition, the quantitative results showed that the concentration of L. pneumophila by the MPN method was greater than ISO 11731 and the difference was statistically significant. However, the two methods were different but highly correlated (r = 0.965, p < 0.001). The specificity and sensitivity of the MPN method were 89.85% and 95.73%, respectively. Overall, the results demonstrated that the MPN method has higher sensitivity, a simple operation process and good application prospects in the routine monitoring of L. pneumophila from water samples.
Collapse
|
7
|
Brunello A, Civilini M, De Martin S, Felice A, Franchi M, Iacumin L, Saccomanno N, Vitacolonna N. Machine learning-assisted environmental surveillance of Legionella: A retrospective observational study in Friuli-Venezia Giulia region of Italy in the period 2002–2019. INFORMATICS IN MEDICINE UNLOCKED 2022. [DOI: 10.1016/j.imu.2021.100803] [Citation(s) in RCA: 2] [Impact Index Per Article: 1.0] [Reference Citation Analysis] [Track Full Text] [Journal Information] [Subscribe] [Scholar Register] [Indexed: 11/30/2022] Open
|
8
|
Yang L, Yi W, Sun F, Xu M, Zeng Z, Bi X, Dong J, Xie Y, Li M. Application of Lab-on-Chip for Detection of Microbial Nucleic Acid in Food and Environment. Front Microbiol 2021; 12:765375. [PMID: 34803990 PMCID: PMC8600318 DOI: 10.3389/fmicb.2021.765375] [Citation(s) in RCA: 1] [Impact Index Per Article: 0.3] [Reference Citation Analysis] [Abstract] [Key Words] [Track Full Text] [Download PDF] [Figures] [Journal Information] [Subscribe] [Scholar Register] [Received: 08/27/2021] [Accepted: 10/08/2021] [Indexed: 12/26/2022] Open
Abstract
Various diseases caused by food-borne or environmental pathogenic microorganisms have been a persistent threat to public health and global economies. It is necessary to regularly detect microorganisms in food and environment to prevent infection of pathogenic microorganisms. However, most traditional detection methods are expensive, time-consuming, and unfeasible in practice in the absence of sophisticated instruments and trained operators. Point-of-care testing (POCT) can be used to detect microorganisms rapidly on site and greatly improve the efficiency of microbial detection. Lab-on-chip (LOC) is an emerging POCT technology with great potential by integrating most of the experimental steps carried out in the laboratory into a single monolithic device. This review will primarily focus on principles and techniques of LOC for detection of microbial nucleic acid in food and environment, including sample preparation, nucleic acid amplification and sample detection.
Collapse
Affiliation(s)
- Liu Yang
- Department of Hepatology Division 2, Beijing Ditan Hospital, Capital Medical University, Beijing, China
| | - Wei Yi
- Department of Gynecology and Obstetrics, Beijing Ditan Hospital, Capital Medical University, Beijing, China
| | - Fangfang Sun
- Department of Hepatology Division 2, Beijing Ditan Hospital, Capital Medical University, Beijing, China
| | - Mengjiao Xu
- Department of Hepatology Division 2, Beijing Ditan Hospital, Capital Medical University, Beijing, China
| | - Zhan Zeng
- Department of Hepatology Division 2, Peking University Ditan Teaching Hospital, Beijing, China
| | - Xiaoyue Bi
- Department of Hepatology Division 2, Beijing Ditan Hospital, Capital Medical University, Beijing, China
| | - Jianping Dong
- Department of Infectious Diseases, Haidian Hospital, Beijing Haidian Section of Peking University Third Hospital, Beijing, China
| | - Yao Xie
- Department of Hepatology Division 2, Beijing Ditan Hospital, Capital Medical University, Beijing, China.,Department of Hepatology Division 2, Peking University Ditan Teaching Hospital, Beijing, China
| | - Minghui Li
- Department of Hepatology Division 2, Beijing Ditan Hospital, Capital Medical University, Beijing, China.,Department of Hepatology Division 2, Peking University Ditan Teaching Hospital, Beijing, China
| |
Collapse
|
9
|
Walker JT, McDermott PJ. Confirming the Presence of Legionella pneumophila in Your Water System: A Review of Current Legionella Testing Methods. J AOAC Int 2021; 104:1135-1147. [PMID: 33484265 PMCID: PMC8378878 DOI: 10.1093/jaoacint/qsab003] [Citation(s) in RCA: 17] [Impact Index Per Article: 5.7] [Reference Citation Analysis] [Abstract] [MESH Headings] [Track Full Text] [Download PDF] [Journal Information] [Subscribe] [Scholar Register] [Received: 11/16/2020] [Revised: 12/18/2020] [Accepted: 12/18/2020] [Indexed: 12/24/2022]
Abstract
Legionnaires' disease has been recognized since 1976 and Legionella pneumophila still accounts for more than 95% of cases. Approaches in countries, including France, suggest that focusing risk reduction specifically on L. pneumophila is an effective strategy, as detecting L. pneumophila has advantages over targeting multiple species of Legionella. In terms of assays, the historically accepted plate culture method takes 10 days for confirmed Legionella spp. results, has variabilities which affect trending and comparisons, requires highly trained personnel to identify colonies on a plate in specialist laboratories, and does not recover viable-but-non-culturable bacteria. PCR is sensitive, specific, provides results in less than 24 h, and determines the presence/absence of Legionella spp. and/or L. pneumophila DNA. Whilst specialist personnel and laboratories are generally required, there are now on-site PCR options, but there is no agreement on comparing genome units to colony forming units and action limits. Immunomagnetic separation assays are culture-independent, detect multiple Legionella species, and results are available in 24 h, with automated processing options. Field-use lateral flow devices provide presence/absence determination of L. pneumophila serogroup 1 where sufficient cells are present, but testing potable waters is problematic. Liquid culture most probable number (MPN) assays provide confirmed L. pneumophila results in 7 days that are equivalent to or exceed plate culture, are robust and reproducible, and can be performed in a variety of laboratory settings. MPN isolates can be obtained for epidemiological investigations. This accessible, non-technical review will be of particular interest to building owners, operators, risk managers, and water safety groups and will enable them to make informed decisions to reduce the risk of L. pneumophila.
Collapse
|
10
|
Young C, Smith D, Wafer T, Crook B. Rapid Testing and Interventions to Control Legionella Proliferation following a Legionnaires' Disease Outbreak Associated with Cooling Towers. Microorganisms 2021; 9:microorganisms9030615. [PMID: 33802700 PMCID: PMC8002549 DOI: 10.3390/microorganisms9030615] [Citation(s) in RCA: 5] [Impact Index Per Article: 1.7] [Reference Citation Analysis] [Abstract] [Key Words] [Track Full Text] [Download PDF] [Figures] [Journal Information] [Subscribe] [Scholar Register] [Received: 02/09/2021] [Revised: 03/04/2021] [Accepted: 03/13/2021] [Indexed: 11/16/2022] Open
Abstract
Most literature to date on the use of rapid Legionella tests have compared different sampling and analytical techniques, with few studies on real-world experiences using such methods. Rapid tests offer a significantly shorter feedback loop on the effectiveness of the controls. This study involved a complex of five factories, three of which had a history of Legionella contamination in their cooling water distribution system. Multiple sampling locations were utilised to take monthly water samples over 39 months to analyse for Legionella by both culture and quantitative polymerase chain reaction (qPCR). Routine monitoring gave no positive Legionella results by culture (n = 330); however, samples were frequently (68%) positive by qPCR for Legionella spp. (n = 1564). Legionella spp. qPCR assay was thus found to be a good indicator of cooling tower system health and suitable as a routine monitoring tool. An in-house qPCR limit of 5000 genomic units (GU)/L Legionella spp. was established to trigger investigation and remedial action. This approach facilitated swift remedial action to prevent Legionella proliferation to levels that may represent a public health risk. Cooling tower operators may have to set their own action levels for their own systems; however, in this study, 5000 GU/L was deemed appropriate and pragmatic.
Collapse
Affiliation(s)
| | - Duncan Smith
- Health and Safety Executive, Newcastle NE98 1YX, UK;
| | - Tim Wafer
- Water Solutions Group, Harrogate HG3 1EQ, UK;
| | - Brian Crook
- Health and Safety Executive, Buxton SK17 9JN, UK;
- Correspondence: ; Tel.: +44-203-028-1882
| |
Collapse
|